ADS8 AC contactors, starters and assemblies

The ADS8 range of DOL, DOL Reversing and Star Delta starters with associated overload relays and accessories / spares. Overload relays are supplied separately and enclosures are IP54 metal clad. A higher rated IP65 moulded 9kW DOL starter is also available.

  • IEC / EN60947
  • CE marked

 9kW DOL starter without switch disconnect
 15kW DOL starter without switch disconnect
 15kW DOL starter with switch disconnect
 11kW DOL reversing starter without switch disconnect
 25kW Star Delta starter without switch disconnect
 DOL, DOL reversing, line connected thermal overload relays
 Star Delta, phase connected thermal overload relays
 Replacement contactors, DOL, DOLR & Star Delta Main contactor
 Replacement contactors, Star Delta. Star & Delta contactors
 Replacement coils, DOL, DOL reversing starters
 Replacement coils, Star Delta starters
 Replacement pneumatic timer, Star Delta starter
 Replacement and additional auxiliary contacts
 Circuit diagrams
 Detailed technical details
 Contact Details





28ADSM1X

9kW DOL starter
without switch disconnect

IP 65 moulded surface mounting enclosure, less overload relay.

Maximum
current rating
(AC3) A

Maximum
kW rating AC3
415v 3ph

Control coil 50Hz1
Vac

Eaton list
number

18

9

220-240

28ADSM1X

18

9

380-415

48ADSM1X

1Other control voltages available, contact Eaton

Dimensions 9kW DOL starter without switch disconnect



 Contact Details


TopHome

 


28ADS3X

15kW DOL starter
without switch disconnect

IP 54 metalclad surface mounting enclosure, less overload relay.

Maximum
current rating
(AC3) A

Maximum
kW rating AC3
415v 3ph

Control coil 50Hz1
Vac

Eaton list
number

18

9

220-240

28ADS1X

18

9

380-415

48ADS1X

25

11

220-240

28ADS2X

25

11

380-415

48ADS2X

32

15

220-240

28ADS3X

32

15

380-415

48ADS3X

1Other control voltages available, contact Eaton

Dimensions 15kW DOL starter without switch disconnect



 Contact Details


TopHome

 


28ADSA1X

15kW DOL starter
with switch disconnect

IP 54 metalclad surface mounting enclosure, less overload relay.

Maximum
current rating
(AC3) A

Maximum
kW rating AC3
415v 3ph

Control coil 50Hz1
Vac

Eaton list
number

18

9

220-240

28ADSA1X

18

9

380-415

48ADSA1X

25

11

220-240

28ADSA2X

25

11

380-415

48ADSA2X

32

15

220-240

28ADSA3X

32

15

380-415

48ADSA3X

1Other control voltages available, contact Eaton

Dimensions 15kW DOL starter with switch disconnect



 Contact Details


TopHome

 


48ARD1X

11kW DOL Reversing starter
without switch disconnect

IP 54 metalclad surface mounting enclosure, less overload relay.

Maximum
current rating
(AC3) A

Maximum
kW rating AC3
415v 3ph

Control coil 50Hz1
Vac

Eaton list
number

18

9

220-240

28ARD1X

18

9

380-415

48ARD1X

25

11

220-240

28ARD2X

25

11

380-415

48ARD2X

1Other control voltages available, contact Eaton

Dimensions 11kW DOL reversing starter without switch disconnect
8 X 20.9mm (3/4”) conduit knockouts are provided for cable entry at top, bottom and side of the enclosure and The earth terminal may be reversed for external connection but the components must be assembled in the same order as supplied.



 Contact Details


TopHome

 


28SDA2X18

25kW Star Delta starter
without switch disconnect

IP 54 metalclad surface mounting enclosure, less overload relay.

Maximum
current rating
(AC3) A

Maximum
kW rating AC3
415v 3ph

Control coil 50Hz1
Vac

Eaton list
number

31

15

220-240

28SDA2X18

31

15

380-415

48SDA2X18

43

22

220-240

28SDA3X25

43

22

380-415

48SDA3X25

55

25

220-240

28SDA3X32

55

25

380-415

48SDA3X32

1Other control voltages available, contact Eaton

Dimensions 25kW Star Delta starter without switch disconnect



Star Delta starter enclosure (IP54 to BSEN60529:1992) 20.9mm (3/4”) conduit knockouts are provided for cable entry at top, bottom and side of the enclosure and the earth terminal may be reversed for external connection, but the components must be assembled in the same order as supplied.

*These 20.9mm conduit knockouts (not available on 28/48SDA3X25 or 28/48SDA3X32.

Outline and knockout dimensions
View shows type 28/48SDA2X18 dimensions in brackets ( ) are for types 28/48SDA3X25 and 28/48SDA3X32.


 Contact Details


TopHome

 


8TT92
DOL, DOL reversing, line connected
thermal overload relays

Full load current
A

Motor rating
kW

Eaton list
number

0.63-1

0.37

8TT87

1-1.6

0.55

8TT88

1.6-2.5

1.1

8TT89

2.5-4

1.5

8TT90

4-6

2.2

8TT91

5.5-8

3.7

8TT98

7-10

4

8TT92

10-13

5.5

8TT93

13-18

9

8TT94

18-25

11

8TT104

23-32

15

8TT96


 Contact Details


TopHome


8TT92SD
Star Delta, phase connected
thermal overload relays

Full load current
A

Motor rating
kW

Eaton list
number

4.3-6.9

3

8TT90SD

6.9-10.4

5.5

8TT91SD

9.5-13.8

7

8TT98SD

12.1-17.3

9

8TT92SD

17.3-22.5

11

8TT93SD

22.5-31

15

8TT94SD

31-43

22

8TT104SD

40-55

25

8TT96SD


 Contact Details


TopHome

 


4832VCO

Replacement contactors, DOL, DOL reversing & Star Delta Main contactor

Open contactor, 3 pole with 1NO auxiliary

Maximum
current rating
(AC3) A

Maximum
kW rating AC3
415v 3ph

Control coil 50Hz1
Vac

Eaton list
number

18

9

220-240

2818VCO

18

9

380-415

4818VCO

25

11

220-240

2825VCO

25

11

380-415

4825VCO

32

15

220-240

2832VCO

32

15

380-415

4832VCO

50

25

220-240

2850VCO

50

25

380-415

4850VCO
1Other control voltages available, contact Eaton


 Contact Details


TopHome

 


4832VCOSD

Replacement contactors, Star Delta. Star & Delta contactors

Open contactor, 3 pole with 1NC auxiliary

Maximum
current rating
(AC3) A

Maximum
kW rating AC3
415v 3ph

Control coil 50Hz1
Vac

Eaton list
number

18

9

220-240

2818VCOSD

18

9

380-415

4818VCOSD

25

11

220-240

2825VCOSD

25

11

380-415

4825VCOSD

32

15

220-240

2832VCOSD

32

15

380-415

4832VCOSD

50

25

220-240

2850VCOSD

50

25

380-415

4850VCOSD
1Other control voltages available, contact Eaton


 Contact Details


TopHome

 


8COIL418
Replacement coils, DOL, DOL reversing starters

Maximum
current rating
(AC3) A

Maximum
kW rating AC3
415v 3ph

Control coil 50Hz1
Vac

Eaton list
number

18

9

110

8COIL118

18

9

220-240

8COIL218

18

9

380-415

8COIL418

25

11

110

8COIL132

25

11

220-240

8COIL232

25

11

380-415

8COIL432

32

15

110

8COIL132

32

15

220-240

8COIL232

32

15

380-415

8COIL432

50

25

220-240

8COIL250

50

25

380-415

8COIL450
1Other control voltages available, contact Eaton


 Contact Details


TopHome

 


8COIL418
Replacement coils, Star Delta starters

Maximum
current rating
(AC3) A

Maximum
kW rating AC3
415v 3ph

Control coil 50Hz1
Vac

Eaton list
number

31

15

220-240

8COIL218

31

15

380-415

8COIL418

43

22

220-240

8COIL232

43

22

380-415

8COIL432

55

25

220-240

8COIL232

55

25

380-415

8COIL432
1Other control voltages available, contact Eaton


 Contact Details


TopHome

 


8TA2DS2
Replacement pneumatic timer,
Star Delta starter

Contact rating
AC11, 500v

Ith, Ui 600v

Eaton list
number

6A

10A

8TA2DS2


 Contact Details


TopHome

 


8TA8DN11

Replacement and additional
auxiliary contacts

Suitable for all DOL, DOLR and Star Delta starters.

Description

Contact
configuration

Contact rating
Ith (A) Ui 600v

Eaton list
number *

Side mounting
auxiliary contact

1NO - 1NC

10

8TA8DN11

Front mounting
auxiliary contact

1NO - 1NC

10

8TA1DN11
* Click here for permissible configurations.


 Contact Details


TopHome

 


Circuit diagrams
Detailed wiring diagrams for the ADS8 range of DOL and Star Delta starters.

 Circuit diagrams
 Contact Details


TopHome

 

 


Telephone:

08700 545 333

Facsimile:

08700 540 333

Address:

Eaton MEM, Reddings Lane,
Birmingham B11 3EZ - United Kingdom
 E-mail: ukcommorders@eaton.com
 UK Sales Contacts & Distributors
 Eaton MEM Worldwide

TopHome


© Copyright Eaton Electric Ltd.