Selecting The Correct Motor Starter

Environmental Conditions and Fault Finding Checklist

What Environmental Conditions Apply?
You should ascertain the conditions which prevail where the starter is to be located, i.e. the level of dust in the atmosphere and the likelihood - if any - of contact with water.

The table defines International Protection (IP) ratings appropriate to various environmental conditions. ADS7 metal enclosure starters are rated IP54 which indicates protection against ingress of dust and splashing liquid from any direction. This ensures that the range is perfectly acceptable in the vast majority of applications. However, should a d.o.l. starter be required for a very dusty location (say, a flour mill) or one where sprayed water is frequently encountered (garden centre, green house, car wash), then an IP65 ADS7 moulded enclosure starter should be used.

With regard to ingress of solid foreign bodies indicated by the first characteristic numeral, BS EN 60529:1992 differentiates between protection of the equipment inside the enclosure and personal protection against contact with live parts. Thus IP3X indicates protection of enclosed equipment against ingress of a solid object greater than 2.5mm diameter or thickness; while IP3XD protects the person against contact by a 1mm diameter test probe no longer than 100mm although solid foreign bodies not exceeding 2.5mm diameter can still enter.
(see diagram)

The second characteristic numeral indicates the degree of protection of enclosed equipment with respect to harmful ingress of water. IP rating tables are detailed here.

Coil Voltage
Coils in Eaton MEM starters comprise contactor coils in the case of automatic starters; and no-volt release coils where these are fitted to manual starters. Standard coils are usually rated either 220/240V or 380/415V, 50Hz. On 3-phase, 415V systems, the coil is usually connected between the supply lines. Therefore, a 380/415V coil is required. ADS7 380/415V coil starters are ready-wired in this way. Where other components in a more complex control scheme require use of a 240V coil, a 220/240V coil starter should be selected. In this case, the control circuit must be wired to ensure that the coil circuit operates between one phase and the neutral.

Starters Less Overloads
ADS7 starters are supplied without overload relays which should be selected separately to suit the application.

Selection of starter and appropriate overload (see below) is very simple and once again merely requires voltage, f.l.c. and kW rating to be established from the motor rating plate.

Ideally an overload relay should be selected whose current scale corresponds at its upper end with the motor f.l.c. It can this be adjusted downwards to the motor's running current if this is known. However, adequate protection is obtained if the overload relay's scale pointer is set to the motor f.l.c.

Fault Find Checklist
Experience has shown that complaints about starter malfunction usually stem from incorrect installation or the easily-rectified results of rough handling, transit shock, etc. A selection of the most frequently encountered symptoms and their remedies is given below. It is assumed that testing will be carried out by a competent electrician.


Problem

Likely Cause

Remedy

Newly-installed starter with not function.

a) overload disturbed in transit and in tripped position.
b) control wiring incorrect/incomplete.
c) Open circuit on one phase.

Press STOP/RESET button.

Check circuit.

Ensure all phases are live on incoming and motor terminals.

Coil overheating.

Wrong coil fitted
(eg, 220/240V coil where should be 380/415V or vice versa. See note opposite).

Change coil to correct type.

Overall relay trips during starting.

a) Overload relays set too far below f.l.c.
b) Motor taking too long to accelerate to full speed.
c) Incorrectly wired main circuit particularly common in single-phase applications.

Adjust overload relay setting.
Check motor is adequately rated for driven load. Check volt drop on supply is within recommended limits.

Wire in accordance with appropriate diagram below.
(Because the overload relay is phase-failure sensitive for additional motor protection in the case of phase loss it is always necessary to include all 3 poles in the main circuit).

*Where possible, select current range to correspond with the motor nameplate rating. kW and hp figures are typical only and may not apply to all types of motor.

Typical Diagrams for 3-phase, single phase and DC Operation


Problem

Likely Cause

Remedy

Noisy or overheated contactor.

a) Intermittent contact in control circuit.
b) Dusty magnet faces owing to pollution by foreign bodies during installation.

Check all auxiliary contacts and remote switches for effective contact. Clean magnet faces.

Excessive contact burning or welding.

a) Excessive voltage drop causing magnet to unseat.
b) Intermittent contact in control circuit causing contactor to chatter.
c) Contactor making or breaking on severe fault.

Check supply voltage is within recommended limit. Check all auxiliary contacts and switches for effective contact.
Check co-ordination of main fuse or MCB (
see here).

Unable successfully to connect pressure switch into control circuit.

Confusion over correct control circuit to be used.

Consult starter instruction leaflet or Eaton MEM catalogue wiring diagram and use appropriate "REMOTE 2 - WIRE (SWITCH) CONTROL" circuit.


Further advice can be obtained from Eaton MEMs Technical Services Department, telephone number 0121-685 2001.



 Selecting The Correct Motor Starter - Main Menu
 The Guide - Main Menu


TopHome


© Copyright Eaton Electric Ltd.