Circuit Breaker Data

Memshield 2 ACB

Type of Device
Rated Voltage
Frequency
Short Circuit Category
= Air Circuit Breaker (MCCB)
= 1000 Volts AC
= 50 Hertz
= Refer to ACB Catalogue


Maximum Earth Loop Impedance Zs (OHMS):

In (A)

Socket Outlet
Circuits (0.4 secs)

Fixed Appliance
Circuits (5 secs)

S/C set to min.

S/C set to max.

S/C set to min.

S/C set to max.

80

3.000

0.300

3.000

0.300

160

1.500

0.150

1.500

0.150

250

0.960

0.096

0.960

0.096

320

0.750

0.075

0.750

0.075

500

0.480

0.048

0.480

0.048

630

0.380

0.038

0.380

0.038

1000

0.240

0.024

0.240

0.024

1250

0.192

0.0192

0.192

0.0192

1600

0.150

0.015

0.150

0.015

2000

0.120

0.012

0.120

0.012

2500

0.096

0.0096

0.096

0.0096

3200

0.075

0.0075

0.075

0.0075

4000

0.060

0.006

0.060

0.006

Disconnection Time/Current Data S/C Set to Min:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

80

80.00

80.00

80.00

80.00

80.00

80.00

160

160.00

160.00

160.00

160.00

160.00

160.00

250

250.00

250.00

250.00

250.00

250.00

250.00

320

320.00

320.00

320.00

320.00

320.00

320.00

500

500.00

500.00

500.00

500.00

500.00

500.00

630

630.00

630.00

630.00

630.00

630.00

630.00

1000

1000.00

1000.00

1000.00

1000.00

1000.00

1000.00

1250

1250.00

1250.00

1250.00

1250.00

1250.00

1250.00

1600

1600.00

1600.00

1600.00

1600.00

1600.00

1600.00

2000

2000.00

2000.00

2000.00

2000.00

2000.00

2000.00

2500

2500.00

2500.00

2500.00

2500.00

2500.00

2500.00

3200

3200.00

3200.00

3200.00

3200.00

3200.00

3200.00

4000

4000.00

4000.00

4000.00

4000.00

4000.00

4000.00

Disconnection Time/Current Data S/C Set to Max:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

80

204.00

480.00

800.00

800.00

800.00

800.00

160

408.00

960.00

1600.00

1600.00

1600.00

1600.00

250

674.00

1500.00

2500.00

2500.00

2500.00

2500.00

320

816.00

1920.00

3200.00

3200.00

3200.00

3200.00

500

1275.00

3000.00

5000.00

5000.00

5000.00

5000.00

630

1605.00

3780.00

6300.00

6300.00

6300.00

6300.00

1000

2550.00

6000.00

10000.00

10000.00

10000.00

10000.00

1250

3188.00

7500.00

12500.00

12500.00

12500.00

12500.00

1600

4080.00

9600.00

16000.00

16000.00

16000.00

16000.00

2000

5100.00

12000.00

20000.00

20000.00

20000.00

20000.00

2500

6375.00

15000.00

25000.00

25000.00

25000.00

25000.00

3200

8160.00

19200.00

32000.00

32000.00

32000.00

32000.00

4000

10200.00

24000.00

40000.00

40000.00

40000.00

40000.00

Maximum Let Through Energy:

Prospective Short Circuit (kA)

0.1

0.2

0.5

1.0

2.0

5.0

10.0

20.0

35.0

40.0

50.0

65.0

85.0

In (A)

I²t (A² sec)

630

800

-

20000

8000

-

2000000

8000000

30000000

100000000

-

-

-

-

1250

-

3000

-

8000

-

2000000

8000000

30000000

-

120000000

-

320000000

-

1600

-

3000

-

8000

-

2000000

8000000

30000000

-

120000000

-

320000000

-

2000

-

3000

-

8000

-

2000000

8000000

30000000

-

120000000

-

320000000

-

2500

-

3000

-

8000

-

2000000

8000000

30000000

-

120000000

-

320000000

-

3200

-

-

-

-

300000

2000000

8000000

30000000

-

120000000

200000000

-

600000000

4000

-

-

-

-

300000

2000000

8000000

30000000

-

120000000

200000000

-

600000000


 Back to Circuit Breaker Data
 The Guide - Main Menu


TopHome


© Copyright Eaton Electric Ltd.