Circuit Breaker Data

Memshield 2 F Frame

Type of Device
Rated Voltage
Frequency
Short Circuit Category
= Moulded Case Circuit Breaker (MCCB)
= 690 Volts AC
= 50/60 Hertz
= Icu 25/45/65kA (415 Volts)


Maximum Earth Loop Impedance Zs (OHMS):

In (A)

Socket Outlet
Circuits (0.4 secs)

Fixed Appliance
Circuits (5 secs)

Standard

Adjustable
S/C set to min.

Adjustable
S/C set to max.

Standard

Adjustable
S/C set to min.

Adjustable
S/C set to max.

16

1.500

-

-

2.000

-

-

20

1.200

-

-

1.600

-

-

32

0.75

-

-

0.960

-

-

40

0.600

-

-

0.730

-

-

50

0.480

0.800

0.400

0.550

0.800

0.400

63

0.380

0.640

0.317

0.400

0.640

0.317

80

0.300

0.500

0.250

0.300

0.500

0.250

100

0.240

0.400

0.200

0.240

0.400

0.200

125

0.192

0.320

0.160

0.192

0.320

0.160

160

0.150

0.250

0.125

0.150

0.250

0.125

200

0.120

-

-

0.120

-

-

Disconnection Time/Current Data Standard:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

16

40.00

80.00

120.00

160.00

160.00

160.00

20

48.00

100.00

150.00

200.00

200.00

200.00

32

70.00

150.00

250.00

320.00

320.00

320.00

40

110.00

240.00

330.00

400.00

400.00

400.00

50

150.00

320.00

440.00

500.00

500.00

500.00

63

190.00

470.00

600.00

630.00

630.00

630.00

80

240.00

600.00

800.00

800.00

800.00

800.00

100

290.00

680.00

1000.00

1000.00

1000.00

1000.00

125

350.00

1000.00

1250.00

1250.00

1250.00

1250.00

160

480.00

1250.00

1600.00

1600.00

1600.00

1600.00

200

600.00

1600.00

2000.00

2000.00

2000.00

2000.00

MCCB Let Through Energy Data I²t (A² sec) F-Frame (Fixed Trip)

Fault Level (A)

Rating

16A

20A

32A

40A

50A

63A

80A

100A

125A

160A

200A

45000

390,000

390,000

700,000

910,000

1,100,000

1,100,000

1,150,000

1,150,000

1,150,000

1,300,000

1,300,000

30000

350,000

350,000

600,000

750,000

830,000

830,000

920,000

920,000

920,000

1,100,000

1,100,000

25000

340,000

340,000

580,000

700,000

800,000

800,000

900,000

900,000

900,000

1,000,000

1,000,000

20000

310,000

310,000

480,000

580,000

650,000

650,000

700,000

700,000

700,000

800,000

800,000

16000

290,000

290,000

410,000

500,500

550,000

550,000

600,000

600,000

600,000

700,000

700,000

5000

120,000

120,000

130,000

140,000

145,000

145,000

148,000

148,000

148,000

150,000

150,000

3000

60,000

60,000

62,000

63,000

66,000

66,000

68,000

68,000

68,000

69,000

69,000

2000

35,000

35,000

35,000

35,000

35,000

35,000

35,000

35,000

35,000

35,000

35,000

Disconnection Time/Current Data Adjustable S/C Set to Min:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

50

165.00

300.00

300.00

300.00

300.00

300.00

63

250.00

378.00

378.00

378.00

378.00

378.00

80

350.00

480.00

480.00

480.00

400.00

480.00

100

450.00

600.00

600.00

600.00

600.00

600.00

125

700.00

750.00

750.00

750.00

750.00

750.00

160

800.00

960.00

960.00

960.00

960.00

960.00

Disconnection Time/Current Data Adjustable S/C Set to Max:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

50

165.00

450.00

600.00

600.00

600.00

600.00

63

250.00

650.00

756.00

756.00

756.00

756.00

80

350.00

960.00

960.00

960.00

960.00

960.00

100

450.00

1050.00

1200.00

1200.00

1200.00

1200.00

125

700.00

1500.00

1500.00

1500.00

1500.00

1500.00

160

800.00

1850.00

1920.00

1920.00

1920.00

1920.00


 Back to Circuit Breaker Data
 The Guide - Main Menu


TopHome


© Copyright Eaton Electric Ltd.