Circuit Breaker Data

Memshield 2 G Frame

Type of Device
Rated Voltage
Frequency
Short Circuit Category
= Moulded Case Circuit Breaker (MCCB)
= 500 Volts AC
= 50/60 Hertz
= Icu 16/25kA (415 Volts)


Maximum Earth Loop Impedance Zs (OHMS):

In (A)

Socket Outlet
Circuits (0.4 secs)

Fixed Appliance
Circuits (5 secs)

16

0.500

1.714

20

0.500

2.000

32

0.500

0.889

40

0.267

0.267

50

0.267

0.267

63

0.267

0.267

80

0.160

0.282

100

0.160

0.200

125

0.160

0.1714

Disconnection Time/Current Data:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

16

38.00

80.00

140.00

480.00

480.00

480.0

20

47.00

90.00

120.00

370.00

480.00

480.00

32

85.00

175.00

270.00

480.00

480.00

480.00

40

140.00

470.00

900.00

900.00

900.00

900.00

50

160.00

500.00

900.00

900.00

900.00

900.00

63

205.00

500.00

900.00

900.00

900.00

900.00

80

270.00

600.00

850.00

1500.00

1500.00

1500.00

100

290.00

720.00

1200.00

1500.00

1500.00

1500.00

125

405.00

900.00

1400.00

1500.00

1500.0

1500.0

MCCB Let Through Energy Data I²t (A² sec) G-Frame

Fault Level (A)

Rating

16A

20A

32A

40A

50A

63A

80A

100A

125A

25000

360,000

360,000

500,000

525,000

630,000

630,000

660,000

660,000

660,000

16000

300,000

300,000

400,000

480,000

530,000

530,000

580,000

580,000

580,000

5000

220,000

220,000

295,000

320,000

360,000

360,000

400,000

400,000

400,000

3000

125,000

125,000

150,000

160,000

180,000

180,000

220,000

220,000

220,000

2000

35,000

35,000

36,000

36,500

40,000

40,000

47,000

47,000

47,000

1500

20,000

20,000

20,000

20,000

20,000

20,000

20,000

20,000

20,000


 Back to Circuit Breaker Data
 The Guide - Main Menu


TopHome


© Copyright Eaton Electric Ltd.