Circuit Breaker Data

Memshield 2 J Frame

Type of Device
Rated Voltage
Frequency
Short Circuit Category
= Moulded Case Circuit Breaker (MCCB)
= 690 Volts AC
= 50/60 Hertz
= Icu 36/65kA (415 Volts)


Maximum Earth Loop Impedance Zs (OHMS):

In (A)

Socket Outlet
Circuits (0.4 secs)

Fixed Appliance
Circuits (5 secs)

Adjustable
S/C set to min.

Adjustable
S/C set to max.

Adjustable
S/C set to min.

Adjustable
S/C set to max.

200

0.200

0.100

0.200

0.100

250

0.160

0.080

0.160

0.080

Disconnection Time/Current Data Adjustable S/C Set to Min:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

200

600.00

1200.00

1200.00

1200.00

1200.00

1200.00

250

1000.00

1500.00

1500.00

1500.00

1500.00

1200.00

Disconnection Time/Current Data Adjustable S/C Set to Max:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

200

600.00

2400.00

2400.00

2400.00

2400.00

2400.00

250

1000.00

3000.00

3000.00

3000.00

3000.00

3000.00

MCCB Let Through Energy Data I²t (A² sec) J-Frame

Fault Level (A)

Rating

160A

200A

250A

65000

1,500,000

2,300,000

3,400,000

50000

1,300,000

2,200,000

3,100,000

36000

1,150,000

1,700,000

2,700,000

25000

1,000,000

1,400,000

2,400,000

16000

700,000

1,100,000

1,800,000

10000

420,000

620,000

1,150,000

5000

190,000

230,000

390,000

3000

90,000

95,000

125,000

2500

62,000

65,000

85,000


 Back to Circuit Breaker Data