Circuit Breaker Data

Memshield 2 K Frame

Type of Device
Rated Voltage
Frequency
Short Circuit Category
= Moulded Case Circuit Breaker (MCCB)
= 690 Volts AC
= 50/60 Hertz
= Icu 36/65kA (415 Volts)


Maximum Earth Loop Impedance Zs (OHMS):

In (A)

Socket Outlet
Circuits (0.4 secs)

Fixed Appliance
Circuits (5 secs)

Adjustable
S/C set to min.

Adjustable
S/C set to max.

Adjustable
S/C set to min.

Adjustable
S/C set to max.

250

-

-

-

-

320

0.125

0.0625

0.125

0.0625

400

0.100

0.050

0.100

0.050

Disconnection Time/Current Data Adjustable S/C Set to Min:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

250

-

-

-

-

-

-

320

900.00

1920.00

1920.00

1920.00

1920.00

1920.00

400

1500.00

2400.00

2400.00

2400.00

2400.00

2400.00

Disconnection Time/Current Data Adjustable S/C Set to Max:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

250

-

-

-

-

-

-

320

900.00

2500.00

3840.00

3840.00

3840.00

3840.00

400

1500.00

4800.00

4800.00

4800.00

4800.00

4800.00

MCCB Let Through Energy Data I²t (A² sec) K-Frame

Fault Level (A)

Rating

250A

320A

400A

65000

3,500,000

4,300,000

5,500,000

50000

3,250,000

4,000,000

5,100,000

36000

2,700,000

3,400,000

4,000,000

30000

2,500,000

3,100,000

3,800,000

20000

2,000,000

2,500,000

3,000,000

16000

1,700,000

2,100,000

2,600,000

10000

1,000,000

1,200,000

1,500,000

5000

380,000

400,000

440,000

4000

220,000

240,000

250,000


 Back to Circuit Breaker Data
 The Guide - Main Menu


TopHome


© Copyright Eaton Electric Ltd.