Circuit Breaker Data

Memshield 2 L Frame

Type of Device
Rated Voltage
Frequency
Short Circuit Category
= Moulded Case Circuit Breaker (MCCB)
= 690 Volts AC
= 50/60 Hertz
= Icu 50kA (415 Volts)


Maximum Earth Loop Impedance Zs (OHMS):

In (A)

Socket Outlet
Circuits (0.4 secs)

Fixed Appliance
Circuits (5 secs)

Adjustable
S/C set to min.

Adjustable
S/C set to max.

Adjustable
S/C set to min.

Adjustable
S/C set to max.

400

0.120

0.060

0.120

0.060

630

0.076

0.038

0.076

0.038

800

0.060

0.030

0.060

0.030

Disconnection Time/Current Data Adjustable S/C Set to Min:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

400

1500.00

2000.00

2000.00

2000.00

2000.00

2000.00

630

2800.00

3150.00

3150.00

3150.00

3150.00

3150.00

800

4000.00

4000.00

4000.00

4000.00

4000.00

4000.00

Disconnection Time/Current Data Adjustable S/C Set to Max:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

400

1500.00

4000.00

4000.00

4000.00

4000.00

4000.00

630

2800.00

6300.00

6300.00

6300.00

6300.00

6300.00

800

4000.00

8000.00

8000.00

8000.00

8000.00

8000.00

MCCB Let Through Energy Data I²t (A² sec) L-Frame (Thermal/Mag)

Fault Level (A)

Rating

400A

630A

800A

50000

12,500,000

12,500,000

12,500,000

40000

10,000,000

10,000,000

10,000,000

35000

9,000,000

9,000,000

9,000,000

30000

7,800,000

7,800,000

7,800,000

20000

6,000,000

6,000,000

6,000,000

15000

4,200,000

4,200,000

4,200,000

10000

2,500,000

2,500,000

2,500,000


 Back to Circuit Breaker Data
 The Guide - Main Menu


TopHome