Circuit Breaker Data

Memshield 2 L, M & N Frame Electronic

Type of Device
Rated Voltage
Frequency
Short Circuit Category
= Moulded Case Circuit Breaker (MCCB)
= 690 Volts AC
= 50/60 Hertz
= Icu 50kA (415 Volts)


Maximum Earth Loop Impedance Zs (OHMS):

In (A)

Socket Outlet
Circuits (0.4 secs)

S/C Set to Min.

S/C Set to Max.

L Frame

M Frame

N Frame

L Frame

M Frame

N Frame

630

0.190

-

-

0.038

-

-

800

0.150

-

-

0.030

-

-

1000

-

0.120

-

-

0.024

-

1250

-

0.096

-

-

0.0192

-

1600

-

-

0.075

-

-

0.015

Maximum Earth Loop Impedance Zs (OHMS):

In (A)

Fixed Appliance Circuits (5 secs)

S/C Set to Min.

S/C Set to Max.

L Frame

M Frame

N Frame

L Frame

M Frame

N Frame

630

0.190

-

-

0.038

-

-

800

0.150

-

-

0.030

-

-

1000

-

0.120

-

-

0.024

-

1250

-

0.096

-

-

0.0192

-

1600

-

-

0.075

-

-

0.015

Disconnection Time/Current Data L Frame Electronic S/C Set to Min:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

630

1260.00

1260.00

1260.00

1260.00

1260.00

1260.00

800

1600.00

1600.00

1600.00

1600.00

1600.00

1600.00

Disconnection Time/Current Data L Frame Electronic S/C Set to Max:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

630

2237.00

5292.00

6300.00

6300.00

6300.00

6300.00

800

2840.00

6720.00

8000.00

8000.00

8000.00

8000.00

Disconnection Time/Current Data M Frame Electronic S/C Set to Min:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

1000

2000.00

2000.00

2000.00

2000.00

2000.00

2000.00

1250

2500.00

2500.00

2500.00

2500.00

2500.00

2500.00

Disconnection Time/Current Data M Frame Electronic S/C Set to Max:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

1000

3500.00

8400.00

10000.00

10000.00

10000.00

10000.00

1250

4438.00

10500.00

12500.00

12500.00

12500.00

12500.00

Disconnection Time/Current Data N Frame Electronic S/C Set to Min:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

1600

3200.00

3200.00

3200.00

3200.00

3200.00

3200.00

Disconnection Time/Current Data N Frame Electronic S/C Set to Max:

Disconnection
Time (s)

60.00

10.00

5.00

1.00

0.40

0.10

In (A)

Disconnection Current (A)

1600

5680.00

13440.00

16000.00

16000.00

16000.00

16000.00

MCCB Let Through Energy Data I²t (A² sec) L-Frame (Electronic)

Fault Level (A)

Rating

630/800A

50000

13,000,000

40000

11,000,000

30000

9,000,000

20000

6,400,000

15000

5,000,000

10000

3,000,000

MCCB Let Through Energy Data I²t (A² sec) M-Frame (Electronic)

Fault Level (A)

Rating

1000/1250A

65000

68,000,000

50000

50,000,000

40000

37,000,000

30000

24,000,000

20000

11,000,000

MCCB Let Through Energy Data I²t (A² sec) N-Frame (Electronic)

Fault Level (A)

Rating

1600A

85000

88,000,000

65000

68,000,000

50000

50,000,000

40000

37,000,000

30000

25,000,000

20000

11,000,000


 Back to Circuit Breaker Data