|
|
Protection
of Cables Miniature and Moulded Case Circuit Breakers |
|
Protection of cables in accordance with the 16th Edition of the IEE Wiring Regulations (BS 7671). Protection
Against Overcurrent Protection
Against Overload Regulation 433-01-01 of the 16th Edition of the IEE Wiring Regulations defines the basic requirement for overload protection, "protective devices shall be provided to break an overload current flowing in the circuit conductors before such a current could cause a temperature rise detrimental to insulation, joints, terminations, or the surroundings of the conductors. Circuits shall be so designed that a small overload of long duration is unlikely to occur". Co-ordination
Between Conductors and Protective Devices a) Ib Miniature circuit breakers and moulded case circuit breakers normally have tripping factors of, or below this 1.45 figure so that if either of these devices is used in compliance with condition a) above will mean that condition b) is also met, thus providing overload protection to the conductors concerned. Protection
Against Short Circuit Protection
of Cables & Conductors Against Short Circuits "The time 't' in which a given short circuit current will raise the temperature of the conductors to the limiting temperature, can be calculated from the formula":-
e.g. for
a p.v.c. insulated copper conductor k = 115 (see table below)
for a few of the k values quoted in the 16th Edition of the IEE
Wiring Regulations. |
|
Material |
Material |
Initial Temp. |
Final Temp. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Note: Where two values of limiting final temperature and of k are given the lower value relates to cables having conductors of greater than 300mm² cross-sectional area. | ||||
|
Therefore if the circuit breaker protecting the cable operates in less time than that required for the cable to reach its temperature limit the cable is protected (see example below, case A). Assessment of protection under short circuit condition when based on the adiabatic equation is only accurate for faults of short duration e.g. less than 0.1 seconds as the equation assumes no heat loss from the cable. IEE Wiring Regulation 434-03-03 also states that for a short circuit duration less than 0.1 seconds, where the asymmetry of the current is of less importance the value of k² s² for the cable should be greater than the energy let through (I²t) of the short circuit protective device (see below, case B). |
|
|
||
|
| Plot the k² s² value for 70mm² p.v.c. insulated copper cable, onto the total energy curve and ensure that the total I²t at the chosen prospective fault is lower for the circuit breaker. Therefore the cable is protected as the breaker trips quicker than the time it takes for the cable to reach its limiting temperature and the k² s² for the cable is higher than the I²t for the circuit breaker (see above). |
|
|
||
|
|