Motor Circuit Protection; Selectivity
Circuit Breakers


Circuit Breaker Selection Charts for Selectivity with Direct-On-Line & Star-Delta Starters

Direct-On-Line:
Typically direct-on-line (d.o.l.) starting will create a start-up current inrush of 6 - 8 x full load current. In addition this inrush can take several seconds to begin to fall to full load current (f.l.c.).

For selectivity with circuit breakers this start-up characteristic must not 'trip' the circuit breaker (see below).

Circuit breaker characteristic curve MDH310  
Typical d.o.l. motor circuit characteristic 2.2kW 3ph.  


Star-Delta

Star-delta starting circuits exhibit lower starting currents than d.o.l., typically 3 - 4 x full load current. However, a transient peak is normally associated with the changeover from star to delta. Hence MEM recommends that the same selection tables are used for both d.o.l. and star-delta starting circuits.

 
Three Phase Motors @ 415V

kW

F.L.C.
(Ie)

MCB
Rating
Type C
(A)

MCB
Rating
Type D
(A)

MCCB
Rating
G
Frame
(A)

MCCB
Rating
F
Frame (A)

MCCB
Rating
J
Frame
(A)

MCCB
Rating
K
Frame
(A)

MCCB
Rating
L
Frame
(A)

Fuselinks
D.O.L.
STD
Fuse
(A)

Motor
Rated
Fuse

STD
Fixed
Trip

Adj.
Trip

0.37

1.3

4

2

-

-

-

-

-

-

6

-

0.56

1.6

4

2

-

-

-

-

-

-

6

-

0.75

1.8

4

2

-

-

-

-

-

-

10

-

1.1

2.6

6

4

-

-

-

-

-

-

10

-

1.5

3.4

6

6

-

-

-

-

-

-

10

-

2.2

5

10

10

-

-

-

-

-

-

16

-

3

6.5

13

13

-

-

-

-

-

-

16

-

3.7

8

16

13

-

-

-

-

-

-

20

-

4

8

16

13

16

16

-

-

-

-

20

20M25

5.5

11

20

20

20

20

-

-

-

-

25

20M32

7.5

15

32

25

32

32

-

-

-

-

40

32M40

9.3

18

32

32

32

32

-

-

-

-

40

32M40

10

20

40

32

40

40

-

-

-

-

50

32M50

11

22

40

40

40

40

-

-

-

-

50

32M50

15

28

50

50

50

50

50

-

-

-

63

32M63

18.5

36

63

63

63

63

63

-

-

-

80

63M80

22

39

63

63

80

80

63

-

-

-

80

63M80

30

52

-

-

100

100

80

-

-

-

100

63M100

37

69

-

-

125

125

100

-

-

-

160

100M160

45

79

-

-

-

160

125

-

-

-

160

100M160

55

96

-

-

-

200

160

-

-

-

200

100M200

75

125

-

-

-

-

-

200

-

-

200

200M250

90

156

-

-

-

-

-

250

-

-

250

200M250

110

189

-

-

-

-

-

250

320

-

315

200M315

132

224

-

-

-

-

-

-

400

-

355

315M400

150

255

-

-

-

-

-

-

400

-

400

315M400

160

275

-

-

-

-

-

-

400

630

450

-

185

318

-

-

-

-

-

-

-

800

500

-

200

339

-

-

-

-

-

-

-

800

500

-
 

Single Phase Motors @ 240V

kW

F.L.C.
(Ie)

MCB
Rating
Type C
(A)

MCB
Rating
Type D
(A)

MCCB
Rating
G Frame
(A)

MCCB
Rating
F
Frame (A)

Fuselinks
D.O.L.
         

STD
Fixed
Trip

Adj.*
Trip
 

0.25

2.6

6

6

-

-

-

10

0.37

3.6

10

10

-

-

-

10

0.56

5

16

13

-

-

-

16

0.75

6.7

20

16

16

16

-

20

1.1

9

25

20

16

32

-

25

1.5

12

32

25

32

32

-

32

2.2

17

50

40

32

40

-

40

3

22

63

50

40

40

-

50

3.7

25

63

63

50

50

50

63

4

27

63

63

50

50

50

63

5.5

38

-

-

63

80

63

100

7.5

50

-

-

80

100

80

100
* Using 3 pole MCCB