Transformer
Protection Circuit Breakers |
|
Due to the inductive windings of transformers a high inrush current is experienced upon 'switch-on'. Typically this can be 10 -15 x full load current of the transformer (In) and is virtually instantaneous. To protect supply lines to the primary windings of a transformer the circuit breaker must provide thermal (long time) protection and magnetic (short time) protection without the device tripping when the transformer is switched on. |
| Circuit breaker characteristic curve MBH132 | |
| Typical 1000VA transformer curve 1ph. |
|
Single
Phase - 240V Transformers Assumed Transformer Inrush Characteristics = 15 x In Selection table for protection of primary transformer windings. For information on selection with lower/higher transformer VA, or lower/higher inrush characteristics please consult our Technical Services Department. |
|||||||
|
|
|
F Frame (A) |
Fuselink STD Fuse (A) |
||||
|
(VA) 240V |
(A) 240V |
Type B (A) |
Type C (A) |
Type D (A) |
G Frame (A) |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Three
Phase - 415V Transformers Assumed Transformer Inrush Characteristics = 15 x In |
|||||||
|
|
|
F Frame (A) |
Fuselink STD Fuse (A) |
||||
|
(VA) 415V |
(A) 415V |
Type B (A) |
Type C (A) |
Type D (A) |
G Frame (A) |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| N.B. All MCCB thermal and magnetic adjustments are assumed to be set at maximum where applicable. For fuselinks, some degree of overloading allowed. For specific examples contact our Technical Services Department. | |||||||
|
|
||
|
|