Thermal De-rating
Circuit Breakers


Thermal de-rating is primarily for environments which create a different ambient temperature. This could be due to temperature variants e.g. Scandinavia, where a re-rating factor is applied or the Middle East where a de-rating factor is applied, close proximity to other warmer operating products and small high IP rated enclosures may also increase the ambient temperature.

Memshield 2 - MCBs & RCBOs Types - B, C, D

Current Ratings
(AMPS)

Device Rating (AMPS)

@40°C

@40°C

@55°C

@60°C

6

6.0

5.4

5.1

10

10.0

9.0

8.5

16

16.0

14.4

13.6

20

20.0

18.0

17.0

32

32.0

28.8

27.2

40

40.0

36.0

34.0

50

50.0

45.0

42.5

63

63.0

56.7

53.6
Memshield 2 MCBs are calibrated at an ambient temperature of 40°C.
50°C calibrated units are available without de-rating.

 

Memshield 2 - G Frame MCCBs Types - MGL, MGH, MGHAT

Current Ratings
(AMPS)

Device Rating (AMPS)

@40°C

@20°C

@30°C

@40°C

@50°C

@60°C

16

19.2

17.6

16.0

14.4

13.0

20

24.0

22.0

20.0

18.0

16.6

32

38.4

35.2

32.0

28.8

26.5

40

48.0

44.0

40.0

36.0

33.2

50

60.0

55.0

50.0

45.0

41.2

63

75.6

69.3

63.0

56.7

52.0

80

96.0

88.0

80.0

72.0

66.0

100

120.0

110.0

100.0

90.0

83.0

125

150.0

137.5

125.0

112.5

104.0

 

Memshield 2 - Fixed Trip F Frame MCCBs Types - MFL, MFH

Current Ratings
(AMPS)

Device Rating (AMPS)

@40°C

@20°C

@30°C

@40°C

@50°C

@60°C

16

19.4

17.8

16.0

14.9

13.6

20

24.2

22.2

20.0

18.6

17.0

32

38.7

35.5

32.0

29.8

27.2

40

48.4

44.4

40.0

37.2

34.0

50

60.5

55.5

50.0

46.5

42.5

63

76.2

69.9

63.0

58.6

53.6

80

96.8

88.8

80.0

74.4

68.0

100

121.0

111.0

100.0

93.0

85.0

125

151.3

138.8

125.0

116.3

106.3

160

193.6

177.6

160.0

148.8

136.0

200

242.0

222.0

200.0

186.0

170.0

 

Memshield 2 - Adjustable Trip F Frame MCCBs Types - MFLA, MFHA

Current Ratings
(AMPS)

Device Rating (AMPS)

@40°C

@20°C

@30°C

@40°C

@50°C

@60°C

50

50.0

50.0

50.0

47.0

44.0

63

63.0

63.0

63.0

59.0

55.0

80

80.0

80.0

80.0

75.0

70.0

100

100.0

100.0

100.0

93.0

88.0

125

125.0

125.0

125.0

117.0

109.0

160

160.0

160.0

160.0

150.0

140.0
NOTE: Adjustable trip F Frame MCCBs require no ambient temp compensation between -5 to 40°C.

 

Memshield 2 - J & K Frame MCCBs Types - MJLA, MJHA, MKLA, MKHA

Current Ratings
(AMPS)

Device Rating (AMPS)

@40°C

@20°C

@30°C

@40°C

@50°C

@60°C

160

160.0

160.0

160.0

150.0

141.0

200

200.0

200.0

200.0

188.0

176.0

250

250.0

250.0

250.0

235.0

220.0

320

320.0

320.0

320.0

304.0

288.0

400

400.0

400.0

400.0

380.0

360.0
NOTE: J & K Frame MCCBs require no ambient temp compensation between -5 to 40°C.

 

Memshield 2 - L Frame MCCBs Types - MLLA

Current Ratings
(AMPS)

Device Rating (AMPS)

@40°C

@20°C

@30°C

@40°C

@50°C

@60°C

400

444.0

424.0

400.0

376.0

350.0

630

699.0

668.0

630.0

590.0

550.0

800

888.0

848.0

800.0

750.0

700.0

 

Memshield 2 - L Frame MCCBs Types - MLLS

Current Ratings
(AMPS)

Device Rating (AMPS)

@40°C

@20°C

@30°C

@40°C

@50°C

@60°C

630

630.0

630.0

630.0

600.0

480.0

800

800.0

800.0

800.0

720.0

608.0

 

Memshield 2 - M & N Frame MCCBs Types - MMLS, MNLS (F&R Connection)

Current Ratings
(AMPS)

Device Rating (AMPS)

@40°C

@20°C

@30°C

@40°C

@50°C

@60°C

1000

1000.0

1000.0

1000.0

1000.0

950.0

1250

1250.0

1250.0

1250.0

1125.0

950.0

1600

1600.0

1600.0

1600.0

1440.0

1216.0

 The Guide - Circuit Breakers - Main Menu
 The Guide - Main Menu


TopHome


© Copyright Eaton Electric Ltd.