High Ambient Air Temperature

Eaton MEM HRC fuse links to BS 88: Part 2: 1988 operate at their stated rating in ambient air temperatures not exceeding 35°C, as required by the standard. ('Ambient air temperatures' are assumed to be temperatures within the enclosures not exceeding 15°C higher than the outside ambient). The following table indicates maximum permissible load currents applicable in high ambient situations, against nominal fuse ratings.

De-rated Currents at Various Ambients:

2A - 20A No De-rating up to and including 60°C ambient.

List No.

Max. Current at Ambient Temperature

40°C

45°C

50°C

55°C

60°C

2SA2

2

2

2

2

2

4SA2

4

4

4

4

4

6SA2

6

6

6

6

6

8SA2

8

8

8

8

8

10SA2

10

10

10

10

10

16SA2

16

16

16

16

16

20SA2

20

20

20

20

20

25SA2

25

25

25

25

25

32SA2

32

32

32

30

28

20SA2M25

20

20

20

20

20

20SA2M32

20

20

20

20

20

2SB3

2

2

2

2

2

4SB3

4

4

4

4

4

6SB3

6

6

6

6

6

8SB3

8

8

8

8

8

10SB3

10

10

10

10

10

16SB3

16

16

16

16

16

20SB3

20

20

20

20

20

25SB3

25

25

25

25

25

32SB3

32

32

31

29

27

32SB3M40

32

32

32

32

29

32SB3M50

32

32

32

32

32

32SB3M63

32

32

32

32

32

40SB4

40

40

40

39

36

50SB4

50

50

50

49

45

63SB4

63

63

63

62

58

63SB4M80

63

63

63

63

63

64SB4M100

63

63

63

63

63

80SD5

80

80

80

80

80

100SD5

100

100

100

93

86

100SD5M125

100

100

100

100

100

100SD5M160

100

100

100

100

100

80SF5

80

80

80

80

77

100SF5

100

100

100

100

92

100SF5M160

100

100

100

100

100

125SD6

125

125

125

125

125

160SD6

160

160

160

160

147

200SD6

200

200

200

185

171

200SD6M250

200

200

200

200

200

125SF6

125

125

125

125

125

160SF6

160

160

160

160

147

200SF6

200

200

200

185

171

200SF6M250

200

200

200

200

200
 

250SF7

250

250

244

228

210

315SF7

315

315

293

274

254

250SG7

250

250

250

250

234

315SG7

314

315

293

275

254
 

355SF8

355

355

338

317

293

400SF8

400

386

364

341

316

355SH8

355

355

342

320

296

400SH8

400

400

378

353

327
 

450SH9

450

450

450

450

431

500SH9

500

500

500

470

435

560SH9

560

560

529

495

459

630SH9

630

614

579

542

502
 

450SY9

450

444

419

392

363

500SY9

500

490

462

432

340

630SY9

569

540

509

476

441
 

710SH10

670

636

599

561

519

800SH10

741

703

663

620

574

710SY10

679

644

607

568

526

800SY10

773

733

692

647

599
 

16SP

16

16

16

16

16

20SP

20

20

20

20

20

25SP

25

25

25

25

25

32SP

32

32

32

32

32

40SP

40

40

40

40

40

50SP

50

50

50

50

50

63SP

63

63

61

58

53
           