Co-ordination with Short Circuit Protective Devices

IEC 60947-4-1 Co-ordination with Short Circuit Protective Devices:
The rated conditional short-circuit current of contactors and starters backed up by short-circuit protective devices(s) (SCPD); combination starters and protected starters shall be verified by short circuit tests as specified.

These tests are mandatory.

Type '1' co-ordination requires that under short-circuit conditions the contactor or starter shall cause no danger to persons or the installation and may not be suitable for further service without repair or replacement of parts.

Type '2' co-ordination requires that under short-circuit conditions the contactor or starter shall cause no danger to persons or the installation and shall be suitable for further use. The risk of contact welding is recognised, in which case the manufacturer shall indicate the measures to be taken as regards the maintenance of the equipment.

Note: Use of an SCPD not in compliance with the manufacturers recommendations may invalidate the co-ordination.

The general requirement for short circuit tests is that contactors and starters intended to be used in enclosures shall be tested in the smallest enclosure stated by the manufacturer.

Type 2 Co-ordination & ADS7 Starters:
The back up fuses quoted give type 2 co-ordination as defined in BS EN 60947-4-1 up to 80kA prospective at 415V 3ph. In selected cases it is possible to use Memshield 2 miniature circuit breakers to provide back up protection for automatic starters up to 10kA prospective at 415V 3 phase.


Starter Type

Overload Relay
Current Range A

Back-up Protection

Max HRC
Fuse,
Eaton MEM
'S' Type, A

Type C

Type D

Direct-on-line
380 ... 415V
3-phase

0.15 - 0.22

2

MCH306

MDH306

0.22 - 0.33

2

MCH306

MDH306

0.33 - 0.50

2

MCH306

MDH306

0.50 - 0.74

4

MCH306

MDH306

0.74 - 1.11

6

MCH306

MDH306

1.11 - 1.66

6

MCH306

MDH306

1.66 - 2.50

10

MCH306

MDH306

2.50 - 3.70

16

MCH310

MDH306

3.70 - 5.60

20

MCH316

MDH310

5.60 - 8.40

20M25

MCH320

MDH316

8.40 - 11.90

20M32

MCH320

MDH320

11.40 - 16.00

32M40

MCH340

MDH332

16.00 - 23.00

32M50

MCH340

MDH332

23.00 - 33.00

63M80

MCH363

MDH340

Direct-on-line
220 ... 240V
single phase

0.74 - 1.11

6

MCH106

MDH106

1.11 - 1.66

6

MCH106

MDH106

1.66 - 2.50

10

MCH110

MDH106

2.50 - 3.70

16

MCH110

MDH106

3.70 - 5.60

20

MCH116

MDH110

5.60 - 8.40

20M25

MCH120

MDH116

8.40 - 11.90

20M32

MCH132

MDH120

11.40 - 16.00

32M40

MCH150

MDH132

Star-Delta
380 ... 415V
3-phase

4.80 - 6.40

16

MCH310

MDH310

6.40 - 9.70

20

MCH316

MDH316

9.70 - 14.50

20M25

MCH320

MDH320

14.50 - 20.60

20M32

MCH340

MDH332

19.70 - 27.70

32M40

MCH350

MDH332

26.00 - 42.00

32M63

MCH363

-

38.00 - 57.00

63M80

-

-
Current range must be selected to include actual motor rated full load current.

Starter Type

Starter Size

Back-up Protection
Max HRC Fuse,
MEM 'S' Type, (A)

Heavy duty contactor starters. Direct-on-line 380/550V 3-phase

22DSB

63M100

30DSB

100M160

37DSB

100M160

55DSB

200

90DSB

250

Heavy duty contactor starters. Star-delta 380/550V 3-phase

30YSB

63M100

45YSB

63M100

55YSB

100M160

75YSB

100M160

90YSB

200