| Co-ordination with Short Circuit Protective Devices |
|
IEC
60947-4-1 Co-ordination with Short Circuit Protective Devices: These tests are mandatory. Type '1' co-ordination requires that under short-circuit conditions the contactor or starter shall cause no danger to persons or the installation and may not be suitable for further service without repair or replacement of parts. Type '2' co-ordination requires that under short-circuit conditions the contactor or starter shall cause no danger to persons or the installation and shall be suitable for further use. The risk of contact welding is recognised, in which case the manufacturer shall indicate the measures to be taken as regards the maintenance of the equipment. Note: Use of an SCPD not in compliance with the manufacturers recommendations may invalidate the co-ordination. The general requirement for short circuit tests is that contactors and starters intended to be used in enclosures shall be tested in the smallest enclosure stated by the manufacturer. Type
2 Co-ordination & ADS7 Starters: |
|
|
Current Range A |
|
||
|
Fuse, Eaton MEM 'S' Type, A |
|
|
||
|
380 ... 415V 3-phase |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
220 ... 240V single phase |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
380 ... 415V 3-phase |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Current range must be selected to include actual motor rated full load current. | ||||
|
|
|
Max HRC Fuse, MEM 'S' Type, (A) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|