| Individual Load Models |
|
PLC's, process controllers, fire and security alarm panels, variable speed/frequency drives, CNC controlled machinery, power supplies, and other similar sensitive mission critical commercial and industrial loads require clean power to operate properly. Unfortunately, these systems operate in electrically dirty, transient rich environments. They are often in close proximity to transient generating sources, and in many cases, produce the damaging transients themselves through normal operation. The result is processing errors, system faults, premature component failure leading to increased maintenance requirements, and system downtime. The solution to these problems is the HS-P-SP, HS and HT dedicated load circuit protection models. They cover a full range of AC and DC suppression applications to safeguard dedicated load circuits of all types, and transient susceptibility levels. |
|
|
|
|
|
|
|
|
![]() |
|
| HS-P-SP Range |

| HS - P - SP Models General Specifications |
|
|
Series wired, terminal strip connected, multi-stage hybrid Active Tracking Network (ATN®) transient suppression device with remote alarm capability and 2 pair telecommunication circuit protection. |
|
|
Dedicated single phase AC power circuits feeding PLC's, process controllers, variable speed/frequency drives, CNC controlled machinery, power supplies, and other critical or general purpose loads. |
|
|
10-Year Free Replacement. |
|
|
Recognised components under UL1449 Second Edition, UL1283 Filter, Telecommunications circuit UL497A. |
|
|
ISO
9001: 1994 Quality System Certification BSI FM 30833. |
| HS - P - SP Models Mechanical Specifications |
|
|
High strength ABS plastic enclosure UL94-5VA. |
|
|
Integral mounting feet. Available with optional universal mounting bracket & DIN rail clip. |
|
|
30 amp models - Box terminals, 60 amp models - lugs, L1, N & E in & out. |
|
|
30
amp models 0.9kg. 60 amp models 1.3kg. |
| HS - P - SP Models Electrical & Performance Specifications |
|
|
Multi-stage, hybrid Active Tracking Network (ATN®) utilising circuit encapsulation and Advanced Surge Path Technology. |
|
|
All Mode: Line to neutral & line to line (normal mode) and line to earth & neutral to earth (common mode). |
|
|
50-60Hz. |
|
|
Active < 1 nanosecond. |
|
|
Up to 40dB normal mode, up to 41dB common mode. |
|
|
30 amps or 60 amps rms max. |
|
|
Statscan circuit diagnostics, 1 LED indicator, normally on. Remote alarm via Form C, N/O and N/C volt-free relay contacts. |
| HS - P - SP Models Telecom Protection Specifications |
|
|
Modular jacks for RJ11 (1 pair) or RJ14 (2 pair). Compatible with standard voice grade lines, including ISDN. |
|
|
Maximum continuous operating voltage 127V tip to ring, tip & ring to earth. |
|
|
Up to 1Mbps. |
|
|
10 ohms. |
|
|
|
|
|
Continuous current rating 100mA max. |
|
|
All Mode: Normal/transverse - tip to ring, common/longitudinal Ð tip to ring & ring to earth. |
|
|
| HS - P - SP Models Test Performance Data |
|
|
Continuous Operating Voltage (Vrms) |
|
|
|||
|
|
|
|
|
|||
|
|
|
|
L-E 70V(d) N-E 40V(s) |
L-E 130V(d) N-E 130V(s) |
L-E 230V(d) N-E 380V(s) |
L-E 440V(d) N-E 440V(s) |
|
|
|
|
L-E 80V(d) N-E 50V(s) |
L-E 210V(d) N-E 130V(s) |
L-E 480V(d) N-E 790V(s) |
L-E 960V(d) N-E 920V(s) |
|
|
|
|
L-E 60V(d) N-E 40V(s) |
L-E 130V(d) N-E 120V(s) |
L-E 230V(d) N-E 300V(s) |
L-E 540V(d) N-E 460V(s) |
|
|
|
|
L-E 50V(d) N-E 40V(s) |
L-E 200V(d) N-E 140V(s) |
L-E 490V(d) N-E 780V(s) |
L-E 1000V(d) N-E 950V(s) |
|
Measured
Limiting (Let-Through) Voltage Test Environment: Test waveforms as described in ANSI/IEEE C62.41- 1991 (A1 Ring Wave - 100Khz, 2,000V, 67A, A3 Ring Wave - 100Khz, 2,000V, 200A, B3/C1 Combination Waveform 6,000V 1.2/50µs, 3,000A 8/20µs, C3 Combination Waveform - 20,000V 1.2/50µs, 10,000A 8/20µs). Tests dynamic (d) or static (s), positive polarity. All voltages are peak (+/-10%), oscilloscope time-base 1ms. 180° phase angle voltages measured from the zero crossing, 90° phase angle voltages are measured from the positive peak of the AC sine wave to the positive peak of the surge. All tests performed at the terminals, simulating actual installation conditions. Options offered may result in performance variance. |
|
|
|
|
| HS - P - SP Models Dimensions |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HS Range |

| HS Models General Specifications |
|
|
Series or parallel wired, terminal strip connected, multi-stage hybrid Active tracking Network (ATN®) transient suppression device. |
|
|
Dedicated single phase AC and DC power circuits operating at 5 to 275 VAC and 5 to 300 VDC at up to 10 amps, feeding PLC's, process controllers, fire and security alarm panels, variable speed/frequency drives, CNC controlled machinery, power supplies, UPS systems and other critical or general purpose loads. |
|
|
10-Year Free Replacement. |
|
|
Recognised components under UL1449 Second Edition (120V & 250V models), UL1283 Filter. |
|
|
ISO
9001: 1994 Quality System Certification BSI FM 30833. |
| HS Models Mechanical Specifications |
|
|
High strength ABS plastic enclosure UL94-5VA. |
|
|
Integral mounting feet. Available with optional universal mounting bracket & DIN rail clip. |
|
|
Box terminals, L1, N & E in & out. |
|
|
0.45kg. |
| HS Models Electrical & Performance Specifications |
|
|
Multi-stage, hybrid Active Tracking Network (ATN®) utilising circuit encapsulation and Advanced Surge Path Technology. |
|
|
All Mode: Line to neutral & line to line (normal mode) and line to earth & neutral to earth (common mode). |
|
|
0-60Hz (AC). |
|
|
Active < 1 nanosecond. |
|
|
Up to 46dB normal mode, up to 51dB common mode. |
|
|
10 amps max. |
|
|
Statscan circuit diagnostics, 1 LED indicator, normally on. |
| HS Models Test Performance Data |
|
|
Continuous Operating Voltage (AC Vrms DC Vpk) |
|
|
||
|
|
|
|
|||
|
|
5-38V DC |
|
L-E 100V(s) N-E 80V(s) |
L-E 150V(s) N-E 120V(s) |
L-E 210V(s) N-E 220V(s) |
|
|
24-65V DC |
|
L-E 130V(s) N-E 80V(s) |
L-E 170V(s) N-E 150V(s) |
L-E 230V(s) N-E 220V(s) |
|
|
48-200V DC |
|
L-E 80V(d) N-E 80V(s) |
L-E 230V(d) N-E 230V(s) |
L-E 390V(d) N-E 540V(s) |
|
|
120-300V DC |
|
L-E 140V(d) N-E 80V(s) |
L-E 430V(d) N-E 230V(s) |
L-E 650V(d) N-E 890V(s) |
|
Measured
Limiting (Let-Through) Voltage Test Environment: Test waveforms as described in ANSI/IEEE C62.41- 1991 (A1 Ring Wave - 100Khz, 2,000V, 67A, A3 Ring Wave - 100Khz, 2,000V, 200A B3/C1 Combination Waveform 6,000V 1.2/50µs, 3,000A 8/20µs) Tests dynamic (d) or static (s), positive polarity. All voltages are peak (+/-10%), oscilloscope time-base 1ms. 180° phase angle voltages measured from the zero crossing, 90° phase angle voltages are measured from the positive peak of the AC sine wave to the positive peak of the surge. All tests performed at the terminals, simulating actual installation conditions. Options offered may result in performance variance. |
|
|
|
|
| HS Models Dimensions |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HT Range |

| HT Models General Specifications |
|
|
Series or parallel wired, terminal strip connected, multi-stage hybrid Active tracking Network (ATN®) transient suppression device. |
|
|
Dedicated single phase AC and DC power circuits operating at 5 to 275 VAC and 5 to 300 VDC at up to 30 amps, feeding general purpose loads. |
|
|
10-Year Free Replacement. |
|
|
Recognised components under UL1449 Second Edition (120V & 250V models), UL1283 Filter. |
|
|
ISO
9001: 1994 Quality System Certification BSI FM 30833. |
| HT Models Mechanical Specifications |
|
|
High strength ABS plastic enclosure UL94-5VA. |
|
|
Integral mounting feet. Available with optional universal mounting bracket & DIN rail clip. |
|
|
Box terminals, L1, N & E in & out. |
|
|
0.45kg. |
| HT Models Electrical & Performance Specifications |
|
|
Threshold Suppression Network utilising circuit encapsulation and Advanced Surge Path Technology. |
|
|
All Mode: Line to neutral & line to line (normal mode) and line to earth & neutral to earth (common mode). |
|
|
0-400Hz (AC). |
|
|
|
|
|
Up to 44dB normal mode, up to 45dB common mode. |
|
|
30 amps max. |
|
|
Statscan circuit diagnostics, 1 LED indicator, normally on. |
| HT Models Test Performance Data |
|
|
Continuous Operating Voltage (AC Vrms DC Vpk) |
|
|
||
|
|
|
|
|||
|
|
5-38V DC |
|
L-E 100V(s) N-E 110V(s) |
L-E 150V(s) N-E 180V(s) |
L-E 160V(s) N-E 170V(s) |
|
|
24-65V DC |
|
L-E 130V(s) N-E 140V(s) |
L-E 170V(s) N-E 160V(s) |
L-E 190V(s) N-E 170V(s) |
|
|
48-200V DC |
|
L-E 330V(d) N-E 350V(s) |
L-E 220V(d) N-E 390V(s) |
L-E 270V(d) N-E 440V(s) |
|
|
120-300V DC |
|
L-E 650V(d) N-E 630V(s) |
L-E 410V(d) N-E 650V(s) |
L-E 490V(d) N-E 770V(s) |
|
*
Measured
Limiting (Let-Through) Voltage Test Environment: Test waveforms as described in ANSI/IEEE C62.41- 1991 (A1 Ring Wave - 100Khz, 2,000V, 67A, A3 Ring Wave - 100Khz, 2,000V, 200A B3/C1 Combination Waveform 6,000V 1.2/50µs, 3,000A 8/20µs) Tests dynamic (d) or static (s), positive polarity. All voltages are peak (+/-10%), oscilloscope time-base 1ms. 180° phase angle voltages measured from the zero crossing, 90° phase angle voltages are measured from the positive peak of the AC sine wave to the positive peak of the surge. All tests performed at the terminals, simulating actual installation conditions. Options offered may result in performance variance. |
|
|
|
|