PTX080 / PTE080

The 80KA per phase PTX080 and PTE080 models of the Protector® are designed to safeguard sensitive and mission critical equipment. The industry's Lowest Measured Limiting Voltage performance on switching generated ring wave transients (by far the most common occurrence in electrical systems) assures maximum equipment protection.

The PTX080/PTE080 models provide the industry's best and most effective combination of high performance features. Effective in stand-alone applications, or as part of the MEM System Shield® integrated installation-wide protection plan, the PTX080/PTE080 is the solution when only the best protection available will do.

General Specifications

Description:
Parallel configured, 80kA per phase, 40kA per mode Multi-Circuit Transient Voltage Surge Suppressor (MCTVSS®) with remote alarm capability.

Application:
Location categories B and A, high to low exposure level, sensitive and critical load applications, including distribution boards, final circuit distribution boards and critical load centres.

Warranty:
20-Year Free Replacement.

Unit Listings:
UL1449 Second Edition, UL1283 Filter.

Quality:
ISO 9001: 1994 Quality System Certification
BSI FM 30833.

Mechanical Specifications

Enclosure:
IP66 rated steel weatherproof enclosure.

Mounting:
Internally threaded conduit fittings with user selected placement in up to four positions and multi-point mounting feet.

Connection:
Standard products include approx. 450mm factory fitted stranded cable #10 AWG (6mm²).

Shipping Weight:
Standard products:
PTX = 3.0kg
PTE = 5.5kg

Electrical & Performance Specifications

Circuit Design:
PTX and PTE units feature parallel configured, Threshold Suppression Network™ utilising Transient Control System™ design, circuit encapsulation and Advanced Surge Path Technology™. PTE units also incorporate multi-stage, hybrid Active Tracking Network (ATN®).

Protection Modes:
All Mode: Line to neutral & line to line (normal mode) and line to earth & neutral to earth (common mode).

Supply Frequency:
50-420Hz (50-60Hz with ATN® option).

Response Time:
PTX 1 nanosecond, PTE Active Tracking Network < 1 nanosecond.

EMI/RFI Attenuation:
Up to 39dB normal mode, up to 42dB common mode.

Capacitance:
2µF per mode (PTE Models).
Note: For applications where earth leakage current may be of concern, please cut enhanced N-E ATN® protection link on PTE models, or utilise PTX models.

Circuit Diagnostics:
Statscan™ circuit diagnostics, 1 LED indicator per phase, normally on. Remote alarm via Form C, N/O and Diagnostics:N/C volt-free relay contacts, with internal terminal connections (0.5mm² to 1.0mm²). Optional S.M.A.R.T. diagnostics with surge counter & event history recording.

 Contact Details


TopHome

 

Test Performance Data

List No.

System Configuration

Nominal System Voltage (rms)

ANSI/IEEE C62.41 - 1991 Measured Limiting Voltage Tests

PTE Models A1 Ring Wave 2,000V 67A 180° Phase Angle

All Models B3/C1 Impulse Wave 6,000V 3,000A 90° Phase Angle

All Models C3 Impulse Wave 20,000V 10,000A 90° Phase Angle

PTX080 1P201
PTE088 1P201

SP N & E

200, 208, 220, 230, 240

L-N 80V
L-E 90V
N-E 90V

L-N 530V
L-E 480V
N-E 520V

L-N 820V
L-E 750V
N-E 840V

PTX080 3Y201
PTE080 3Y201

TP N & E
Star Connected

230/380, 230/400, 240/415, 277/480

L-N 80V
L-L 110V
L-E 120V
N-E 100V

L-N 420V
L-L 1000V
L-E 420V
N-E 680V

L-N 900V
L-L 1600V
L-E 1100V
N-E 1200V

Measured Limiting (Let-Through) Voltage Test Environment:
Test waveforms as described in ANSI/IEEE C62.41- 1991 (A1 Ring Wave - 100Khz, 2,000V, 67A, B3/C1 Combination Waveform 6,000V 1.2/50µs, 3,000A 8/20µs, C3 Combination Waveform - 20,000V 1.2/50µs, 10,000A 8/20µs) All modes tested dynamic except N-E, positive polarity. All voltages are peak (+/-10%), oscilloscope time-base 1ms. 180° phase angle voltages measured from the zero crossing, 90° phase angle voltages are measured from the positive peak of the AC sine wave to the positive peak of the surge. All tests performed with a 152.4mm (6-inch) lead length, simulating actual installation conditions. Options offered may result in performance variance.
 Contact Details


TopHome

 

Option Designators

PTX Prefix Models:
Threshold Suppression Network.

PTE Prefix Models:
Active Tracking Network.

Add Suffix SD:
S.M.A.R.T. Diagnostics.

 International Voltage Configurations

 

Dimensions
PTX080


PTE080

 Contact Details


TopHome

 

 

 


Eaton MEM

Telephone:

0121 685 2100

+44 121 685 2100

Facsimile:

0121 706 2012

+44 121 706 2012

Address:

Eaton MEM, Reddings Lane,
Birmingham B11 3EZ - United Kingdom
 E-mail: ukcommorders@eaton.com
 UK Sales Contacts & Distributors
 MEM Worldwide

TopHome


© Copyright Eaton Electric Ltd.