| PTX300 / PTE300 |
|
|
|
|
The 300KA per phase PTX300 and PTE300 models of the Protector® are designed to safeguard a wide range of heavy industrial and commercial systems and equipment protection applications. Installation of the PTX300/PTE300 models provides high peak surge current handling and unmatched suppression of high energy impulse transients. Effective in stand-alone applications, or as part of the MEM System Shield® integrated installation-wide protection plan, the PTX300/PTE300 will provide a lifetime of effective performance with 'fit and forget' durability. |
|
|
|
| General Specifications |
|
|
Parallel configured, 300kA per phase, 150kA per mode Multi-Circuit Transient Voltage Surge Suppressor (MCTVSS®) with remote alarm capability. |
|
|
Location
categories C and B, high exposure level, industrial applications
including large service entrances, large switchboards and large
individual load isolators. |
|
|
20-Year Free Replacement. |
|
|
UL1449 Second Edition, UL1283 Filter. |
|
|
ISO
9001: 1994 Quality System Certification BSI FM 30833. |
| Mechanical Specifications |
|
|
IP66 rated steel weatherproof enclosure. |
|
|
Internally threaded conduit fittings with user selected placement in up to four positions and multi-point mounting feet. |
|
|
Products accommodate 16mm² to 50mm² conductors in box terminals. |
|
|
14kg. |
| Electrical & Performance Specifications |
|
|
PTX and PTE units feature parallel configured, Threshold Suppression Network utilising Transient Control System design, circuit encapsulation and Advanced Surge Path Technology. PTE units also incorporate multi-stage, hybrid Active Tracking Network (ATN®). |
|
|
All Mode: Line to neutral & line to line (normal mode) and line to earth & neutral to earth (common mode). |
|
|
50-420Hz (50-60Hz with ATN® option). |
|
|
PTX
|
|
|
Up to 40dB normal mode, up to 34dB common mode. |
|
|
2µF
per mode (PTE Models). Note: For applications where earth leakage current may be of concern, please cut enhanced N-E ATN® protection link on PTE models, or utilise PTX models. |
|
|
Statscan circuit diagnostics, 1 LED indicator per phase, normally on. Remote alarm via Form C, N/O and Diagnostics:N/C volt-free relay contacts, with internal terminal connections (0.5mm² to 1.0mm²). Optional S.M.A.R.T. diagnostics with surge counter & event history recording. |
|
|
| Test Performance Data |
|
|
|
|
|
||
|
|
|
|
|||
|
PTE300 1P201 |
|
|
L-E 120V N-E 100V |
L-E 550V N-E 900V |
L-E 1100V N-E 1500V |
|
PTE300 3Y201 |
Star Connected |
|
L-L 110V L-E 120V N-E 90V |
L-L 950V L-E 560V N-E 900V |
L-L 1600V L-E 980V N-E 1500V |
|
Measured
Limiting (Let-Through) Voltage Test Environment: Test waveforms as described in ANSI/IEEE C62.41- 1991 (A1 Ring Wave - 100Khz, 2,000V, 67A, B3/C1 Combination Waveform 6,000V 1.2/50µs, 3,000A 8/20µs, C3 Combination Waveform - 20,000V 1.2/50µs, 10,000A 8/20µs) All modes tested dynamic except N-E, positive polarity. All voltages are peak (+/-10%), oscilloscope time-base 1ms. 180° phase angle voltages measured from the zero crossing, 90° phase angle voltages are measured from the positive peak of the AC sine wave to the positive peak of the surge. All tests performed with a 152.4mm (6-inch) lead length, simulating actual installation conditions. Options offered may result in performance variance. |
|
|
| Option Designators |
|
|
Threshold Suppression Network. |
|
|
Active Tracking Network. |
|
|
S.M.A.R.T. Diagnostics. |
|
|
| Dimensions |

|
|
|
|
Eaton MEM | |
|
|
|
|
|
|
|
|
|
|
Birmingham B11 3EZ - United Kingdom |
|
|
|
||
|
|
||
|
|
||