| PTX400 / PTE400 |
|
|
|
|
The 400KA per phase, 200KA per mode PTX400 and PTE400 models of the Protector® are designed to safeguard high priority systems and load equipment in heavy industrial environments and applications. These applications dema nd only the most effective and durable protection available. Installation of the PTX400/PTE400 assures damaging transients are intercepted before they reach critical loads. Effective in stand-alone applications, or as part of the MEM System Shield® integrated installation-wide protection plan, the PTX400/PTE400 is the answer when downtime is not an option. |
|
|
|
| General Specifications |
|
|
Parallel configured, 300kA per phase, 150kA per mode Multi-Circuit Transient Voltage Surge Suppressor (MCTVSS®) with remote alarm capability. |
|
|
Location
categories C and B, high exposure level, industrial applications
including large service entrances, large switchboards and large
individual load isolators. |
|
|
20-Year Free Replacement. |
|
|
UL1449 Second Edition, UL1283 Filter. |
|
|
ISO
9001: 1994 Quality System Certification BSI FM 30833. |
| Mechanical Specifications |
|
|
IP66 rated steel weatherproof enclosure. |
|
|
Internally threaded conduit fittings with user selected placement in up to four positions and multi-point mounting feet. |
|
|
Products accommodate 16mm² to 50mm² conductors in box terminals. |
|
|
14kg. |
| Electrical & Performance Specifications |
|
|
PTX and PTE units feature parallel configured, Threshold Suppression Network utilising Transient Control System design, circuit encapsulation and Advanced Surge Path Technology. PTE units also incorporate multi-stage, hybrid Active Tracking Network (ATN®). |
|
|
All Mode: Line to neutral & line to line (normal mode) and line to earth & neutral to earth (common mode). |
|
|
50-420Hz (50-60Hz with ATN® option). |
|
|
PTX
|
|
|
Up to 40dB normal mode, up to 34dB common mode. |
|
|
2µF
per mode (PTE Models). Note: For applications where earth leakage current may be of concern, please cut enhanced N-E ATN® protection link on PTE models, or utilise PTX models. |
|
|
Statscan circuit diagnostics, 1 LED indicator per phase, normally on. Remote alarm via Form C, N/O and Diagnostics:N/C volt-free relay contacts, with internal terminal connections (0.5mm² to 1.0mm²). Optional S.M.A.R.T. diagnostics with surge counter & event history recording. |
|
|
| Test Performance Data |
|
|
|
|
|
||
|
|
|
|
|||
|
PTE400 3Y201 |
Star Connected |
|
L-L 110V L-E 120V N-E 90V |
L-L 950V L-E 560V N-E 900V |
L-L 1600V L-E 980V N-E 1500V |
|
Measured
Limiting (Let-Through) Voltage Test Environment: Test waveforms as described in ANSI/IEEE C62.41- 1991 (A1 Ring Wave - 100Khz, 2,000V, 67A, B3/C1 Combination Waveform 6,000V 1.2/50µs, 3,000A 8/20µs, C3 Combination Waveform - 20,000V 1.2/50µs, 10,000A 8/20µs) All modes tested dynamic except N-E, positive polarity. All voltages are peak (+/-10%), oscilloscope time-base 1ms. 180° phase angle voltages measured from the zero crossing, 90° phase angle voltages are measured from the positive peak of the AC sine wave to the positive peak of the surge. All tests performed with a 152.4mm (6-inch) lead length, simulating actual installation conditions. Options offered may result in performance variance. |
|
|
| Option Designators |
|
|
Threshold Suppression Network. |
|
|
Active Tracking Network. |
|
|
S.M.A.R.T. Diagnostics. |
|
|
| Dimensions |

|
|
|
|
Eaton MEM | |
|
|
|
|
|
|
|
|
|
|
Birmingham B11 3EZ - United Kingdom |
|
|
|
||
|
|
||
|
|
||