| PTX640 / PTE640 |
|
|
|
The 640kA per phase PTX640 and PTE640 models of the Protector® are designed to safeguard zero tolerance and high priority systems and load equipment in the heaviest industrial environments and applications. These applications demand only the most effective and durable protection available. Installation of the PTX640/PTE640 assures damaging transients are intercepted before they reach critical loads. Effective in stand-alone applications, or as part of the MEM System Shield® integrated installation-wide protection plan, the PTX640/PTE640 is the answer when downtime is not an option. |
|
|
|
| General Specifications |
|
|
Parallel configured, 640kA per phase, Multi-Circuit Transient Voltage Surge Suppressor (MCTVSS®) with remote alarm capability. |
|
|
Location category C, unlimited exposure level, heaviest industrial applications including unlimited capacity service entrances and switchboards, the largest distribution panels and individual load isolators. |
|
|
20-Year Free Replacement. |
|
|
UL1449 Second Edition, UL1283 Filter. |
|
|
ISO
9001: 1994 Quality System Certification BSI FM 30833. |
| Mechanical Specifications |
|
|
IP66 rated steel weatherproof enclosure. |
|
|
Internally threaded conduit fittings with user selected placement in up to four positions and multi-point mounting feet. |
|
|
Products accommodate 16mm² to 50mm² conductors in box terminals. |
|
|
27kg. |
| Electrical & Performance Specifications |
|
|
PTX and PTE units feature parallel configured, Threshold Suppression Network utilising Transient Control System design, circuit encapsulation and Advanced Surge Path Technology. PTE units also incorporate multi-stage, hybrid Active Tracking Network (ATN®). |
|
|
All Mode: Line to neutral & line to line (normal mode) and line to earth & neutral to earth (common mode). |
|
|
50-420Hz (50-60Hz with ATN® option). |
|
|
PTX
|
|
|
Up to 42dB normal mode, up to 41dB common mode. |
|
|
2µF
per mode (PTE Models). Note: For applications where earth leakage current may be of concern, please cut enhanced N-E ATN® protection link on PTE models, or utilise PTX models. |
|
|
Statscan circuit diagnostics, 1 LED indicator per phase, normally on. Remote alarm via Form C, N/O and N/C volt-free relay contacts, with internal terminal connections (0.5mm² to 1.0mm²). Optional S.M.A.R.T. diagnostics with surge counter & event history recording. |
|
|
| Test Performance Data |
|
|
|
|
|
||
|
|
|
|
|||
|
PTE400 3Y201 |
Star Connected |
|
L-L 130V L-E 110V N-E 50V |
L-L 920V L-E 620V N-E 980V |
L-L 1500V L-E 1200V N-E 1600V |
|
Measured
Limiting (Let-Through) Voltage Test Environment: Test waveforms as described in ANSI/IEEE C62.41- 1991 (A1 Ring Wave - 100Khz, 2,000V, 67A, B3/C1 Combination Waveform 6,000V 1.2/50µs, 3,000A 8/20µs, C3 Combination Waveform - 20,000V 1.2/50µs, 10,000A 8/20µs) All modes tested dynamic except N-E, positive polarity. All voltages are peak (+/-10%), oscilloscope time-base 1ms. 180° phase angle voltages measured from the zero crossing, 90° phase angle voltages are measured from the positive peak of the AC sine wave to the positive peak of the surge. All tests performed with a 152.4mm (6-inch) lead length, simulating actual installation conditions. Options offered may result in performance variance. |
|
|
| Option Designators |
|
|
Threshold Suppression Network. |
|
|
Active Tracking Network. |
|
|
S.M.A.R.T. Diagnostics. |
|
|
| Dimensions |

|
|
|
|
Eaton MEM | |
|
|
|
|
|
|
|
|
|
|
Birmingham B11 3EZ - United Kingdom |
|
|
|
||
|
|
||
|
|
||