Modular Contactors

Type
   

AA16

AA20

AA40

AA63

Environment
           

Rated insulation voltage (Ui)

Conforming to IEC 1095

V

500

Conforming to VDE 0110

Rated impulse withstand voltage (Uimp)
 

kV

4 in enclosure

Conforming to standards
   

IEC 61095, VDE 0660 AND BS EN 60947-5 for auxiliary contacts

Approvals
   

NF- USE, VDE, CEBEC, ÖVE

Degree of protection

Conforming to
VDE 0106
 

Protection against direct finger contact
(IP 20 open, IP 40 in enclosure)

Protective treatment

Standard version
 

"TC"

Ambient air temperature around the device

Storage version
Operation

°C
°C

- 40... +70
- 5... +50 (0.85...1.1 Uc)

Maximum operating altitude

Without derating

m

3000

Operating positions

Without derating
 

± 30° in relation to normal
vertical mounting position

Shock resistance
½ sine wave = 10ms

Contactor open
 

10gn

Contactor closed
 

15gn

Vibration resistance
5...300Hz

Contactor open
 

2gn

Contactor closed
 

3gn

Flame resistance
Opacity and toxicity of fumes
   

Conforming to IEC 61095
   

Conforming to NF F 16-101 and 16-102
 Pole Characteristics

Number of poles
   

2, 3 or 4

Rated operational current (Ie)
(Ue
440V)

In AC - 7a
(heating)

A

16

25

40

63

In AC - 7b
(motor control)

A

5

8.5

15

25

Rated operation voltage (Ue)

Up to

V

250 two-pole contactors, 415 three and four-pole contactors

Frequency limits

Of the operational current

Hz

400
     

Conventional thermal current (Ith)

ø50°C

A

16

25

40

63

Rated making and breaking capacity

Conforming to IEC 1095 (AC-7b) I rms 400V 3-phase

A

40

68

120

200

Permissible short time rating with no current flow for the previous 15 minutes and with
ø
40°C

For 10s

A

128

200

320

504

For 30s

A

40

62

100

157

Short-circuit protection by fuse or circuit breaker U440V

gl fuse

A

16

25

40

63

Circuit breaker I²t 230V

s

5000

10000

16000

18000

(at 3 kA rms prospective) 400V

s

9000

14000

17500

20000

Average impedance per pole

At Ith and 50Hz

m ohms

2.5

2.5

2

2

Power dissipated

For the above operational currents

W

0.65

1.6

3.2

8

Maximum cabling c.s.a.
Flexible cable without cable end

1 conductor

mm²

6

6

25

25

2 conductor

mm²

4

4

16

16

Flexible cable with cable end

1 conductor

mm²

6

6

16

16

2 conductor

mm²

1.5

1.5

4

4

Solid cable without cable end

1 conductor

mm²

6

6

25

25

2 conductor

mm²

4

4

6

6

Tightening torque

Power circuit connections

N.m

1.4

1.4

3.5

3.5

Type
Control Circuit
Characteristics
   

AA16 AA20
Single or 2-pole

AA16 AA20
3 or 4-pole

AA40 AA63
3 or 4-pole

AA40 AA63
2-pole
 

Rated control circuit voltage (Uc)

50 or 60 Hz

V

12...240V, for other voltages, please consult us

Control voltage limits
50°C)
50Hz coils

Operational
 

0.85...1.1Uc

Drop out
 

0.2...0.75Uc

Average coil consumption at 20°C and Uc ~ 50 Hz

Inrush

VA

15

34

53

Sealed

VA

3.8

4.6

6.5

Maximum heat dissipation

50/60 Hz

W

1.3

1.6

2.1

Operating times (1)

Closing "C"
Opening "O"

ms
ms

10...30
10...25

Mechanical durability

In operating cycles
 

106

Maximum operating rate at ambient temperature50°C

In operating cycles per hour
 

300

Maximum cabling c.s.a. Flexible cable without cable end

1 or 2 conductors

mm²

2.5

Flexible cable without cable end

1 conductor
2 conductors

mm²
mm²

2.5
1.5

Solid cable without cable end

1 or 2 conductors

mm²

1.5

Tightening torque
 

N.m

1.4
 Instantaneous Auxiliary Contact Characteristics

Rated operational voltage (Ue)

Up to

V

250

Rated insulation
voltage (Ui)

Conforming to
BS EN 60947-5

V

500

Conforming to
VDE 0110

V

500

Conventional thermal current (Ith)

For ambient
ø
50°C

A

5

Mechanical durability

Operating cycles
 

106

Maximum cabling c.s.a.

Flexible or solid conductor

mm²

2.5

Tightening torque
 

N.m

1.4
 

Lighting (Maximum Number of Lamps Depending on the Power of each unit
Presentation of installations according to type of supply:

Single phase circuit, 230 V

3 phase circuit, 230 V

3 phase circuit, 400 V (with neutral)

Lighting (Maximum Number of Lamps Depending on the Power of Each Unit) Continued
The maximum number of lamps which can be operated per phase is equal to the total number of lamps in the "single-phase 230V" table divided by the square root of 3.

The maximum number of lamps which can be operated per phase is equal to the total number of lamps in the "single-phase 230V" table.

Contactor rating indicated below for a single-phase 230 V circuit (single-pole)

 Fluorescent Lamps with Starter

Single Fitting
 

Non Corrected
 

With Parallel Correction
 

Contactor Rating

P in W

20

40

50

80

110

20

40

58

80

110

-

I in A

0.39

0.43

0.70

0.80

1.2

0.19

0.29

0.46

0.57

0.79

-

C in µF

-

-

-

-

-

5

5

7

7

16

-
 

Maximum
number of
Lamps
 

22

20

13

10

7
 

15

15

10

10

5
 

16A

30

28

17

15

10

20

20

15

15

7

25A

70

60

35

30

20

40

40

30

30

14

40A

100

90

56

48

32

60

60

43

43

20

63A
 

Twin Fitting
 

Non Corrected
 

With Series Correction
 

Contactor Rating

P in W

2x18

2x36

2x58

2x80

2x140

2x18

2x36

2x58

2x80

2x140

-

I in A

0.44

0.82

1.34

1.64

2.2

0.26

0.48

0.78

0.96

1.3

-

C in µF

-

-

-

-

-

3.5

4.5

7

9

18

-
 

Maximum
number of
Lamps
 

20

11

7

5

4
 

30

17

10

9

6
 

16A

30

16

10

8

6

46

25

16

13

10

25A

50

26

16

13

10

80

43

27

22

16

40A

75

42

25

21

16

123

67

42

34

25

63A
 

 High Pressure Mercury Vapour Lamps
 

Non Corrected
 

With Parallel Correction
 

Contactor Rating

P in W

50

80

125

250

400

700

50

80

125

250

400

700

1000

-

IB in A

0.6

0.8

1.15

2.15

3.25

5.4

0.35

0.50

0.7

1.5

2.4

4

5.7

-

C in µF

-

-

-

-

-

-

7

8

10

18

25

40

60

-
 

Maximum
number of
Lamps
 

15

10

8

4

2

1
 

10

9

9

4

3

2

-
 

16A

20

15

10

6

4

2

15

13

10

6

4

2

1

25A

34

27

20

10

6

4

28

25

20

11

8

5

3

40A

53

40

28

15

10

6

43

38

30

17

12

7

5

63A
 

 Low Pressure Sodium Vapour Lamps
 

Non Corrected
 

With Parallel Correction
 

Contactor Rating

P in W

18

35

55

90

135

180

18

35

55

90

135

180

-

IB in A

0.35

1.4

1.4

2.1

3.1

3.1

0.35

0.6

0.6

0.9

0.9

0.9

-

C in µF

-

-

-

-

-

-

5

20

20

26

45

40

-
 

Maximum
number of
Lamps
 

18

4

5

3

2

2
 

14

3

3

2

1

1
 

16A

34

9

9

6

4

4

21

5

5

4

2

2

25A

57

14

14

9

6

6

40

10

10

8

4

5

40A

91

24

24

19

10

10

60

15

15

11

6

7

63A
 

 High Pressure Sodium Vapour Lamps
 

Non Corrected
 

With Parallel Correction
 

Contactor Rating

P in W

70

150

250

400

1000

70

150

250

400

1000

-

IB in A

1

1.8

3

4.4

10.3

0.6

0.7

1.5

2.5

6

-

C in µF

-

-

-

-

-

12

12

32

25

45

-
 

Maximum
number of
Lamps
 

8

4

2

1

-
 

6

6

2

2

1
 

16A

12

7

4

3

1

9

9

3

4

2

25A

20

13

8

5

2

18

18

6

8

4

40A

32

18

11

8

3

25

25

9

12

6

63A
 

 Metal Iodine or Halogen Vapour Lamps
 

Non Corrected
 

With Parallel Correction
 

Contactor Rating

P in W

35

70

150

250

400

1000

39

70

150

250

400

1000

2000

-

IB in A

0.3

0.5

1

1.5

2.5

6

0.3

0.5

1

1.5

2.5

6

5.5

-

C in µF

-

-

-

-

-

-

6

12

20

32

45

85

60

-
 

Maximum
number of
Lamps
 

27

16

8

5

3

1
 

12

6

4

3

2

-

1
 

16A

40

24

12

8

5

2

18

9

6

4

3

1

2

25A

68

42

20

14

8

4

31

16

10

7

5

3

3

40A

106

64

32

21

13

5

50

25

15

10

7

4

5

63A